The 36000 BTU Ceiling Cassette from Chigo Air-Conditioning is best suited for home and office use. This aircon will work optimal in rooms with a floor size of up to 60m². Our franchises, agents and dealers are all highly trained professionals and will also be able to assist you with the installation.
Feel free to request a quote or contact us for expert advise.
Type of Unit | CEILING CASSETTE | ||
---|---|---|---|
Model | CCA-36HR1(RS485) | ||
Indoor Power Supply | V-Ph-Hz | 220~240/1/50 | |
Cooling | Capacity | Btu/h | 36000 |
kW | 10.5 | ||
Input | W | 160 | |
Rated current | A | 0.8 | |
EER | W/W | 2.71 | |
Heating | Capacity | Btu/h | 39000 |
Kw | 11.5 | ||
Input | W | 160 | |
Rated current | A | 0.8 | |
COP | w/w | 3.31 | |
Indoor Fan Motor | Model | YDK-75T-6 | |
Input | W | 160 | |
Capacitor | uF | 4 | |
Speed (Hi/Med/Low) | r/min | 760/680/580 | |
Indoor Coil | Number of Rows | 2 | |
Tube Pitch (a) x Row Pitch (b) | mm | 21 x 13.37 | |
Fin Spacing | mm | 1.45 | |
Fin Type | Hydrophilic | ||
Tube Outside Dia. and Type | mm | 7 Inner grooved | |
Coil length x height x width | mm | 2000 x 252 x 26.74 | |
Number of Circuits | 12 | ||
Indoor Airflow (High speed) | m³/h | 1700 | |
Indoor Noise Level | dB(A) | 44~48 | |
Indoor Unit | Dimension (W x D x H) | mm | 840 x 840 x 285 |
Panel | mm | 950 x 950 x 50 | |
Packaging (W x D x H) | mm | 920 x 920 x 310 | |
Panel | mm | 1030 x 1030 x 105 | |
Net/Gross weight | Kg | 28/33.5 | |
Panel | Kg | 5.4/8.0 | |
Max Pressure | MPa | 4.0 | |
Refrigerant | Type | R410a | |
Refrigerant Piping | Liquid Side/Gas Side | mm | 9.52/19.05 (3/8 x 3/4) |
Drainage Pipe | mm | DN25 | |
Standard Controller | Standard controller | ||
Operation Temperature | °C | 16~32 | |
Ambient Temperature | Cooling | °C | 18-50 |
Heating | °C | -7~24 | |
Application Area | m² | 40-70 | |
Model | COU-36HR1 | ||
Outdoor Power Supply | V-Ph-Hz | 220~240/1/50 | |
Cooling | Capacity | Btu/h | 36000 |
Kw | 10.5 | ||
Input | W | 3710 | |
Rated current | A | 16.7 | |
Heating | Capacity | Btu/h | 39000 |
Capacity | Kw | 11.5 | |
Input | W | 3310 | |
Rated current | A | 15 | |
Max Input Consumption | W | 4800 | |
Max Current | A | 21.2 | |
Starting current | A | 112 | |
Compressor | Model | ATH4720MV-C9EU | |
Type | Rotary | ||
Brand | Highly | ||
Capacity | Btu/h | 34324 | |
Input | W | 3470 | |
Rated current (RLA) | A | 16.4 | |
Locked rotor (LRA) | A | 80 | |
Thermal protector | Internal | ||
Capacitor | uF | 90 | |
Refrigerant Oil | ml | 840+-20 | |
Outdoor Motor Fan | Model | YDK-200-6B | |
Input | W | 450 | |
Capacitor | uF | 10 | |
Speed | r/min | 800 | |
Outdoor Coil | Number of rows | 1 | |
Tube Pitch (a) x Row Pitch (b) | mm | 25 x 21.65 | |
Fin spacing | mm | 1.4 | |
Fin type | Hydrophilic | ||
Tube outside dia. and type | mm | 9.52 Inner grooved | |
Coil length x height x width | mm | 883.5 x 950 x 21.65 | |
Number of circuits | 3 | ||
Outdoor Air flow (High speed) | m³h | 6000 | |
Outdoor Noise Level | dB(A) | 65 | |
Outdoor Unit | Dimension (W x D x H) | mm | 1070 x 400 x 995 |
Packaging (W x D x H) | mm | 1145 x 475 x 1120 | |
Net/Gross weight | Kg | 78/86 | |
Refrigerant | Type/Quantity | g | R410a/2200 |
Throttle Part | Capillary | ||
Design Pressure | MPa | 4.0/1.2 | |
Max Pressure | MPa | 4.5 | |
Connecting Wiring | Outdoor power supply | Separated | |
Power wiring | mm | 3 x 4.0/3 x 1.0 | |
Signal wiring | mm | 3 x 0.75 | |
Refrigerant Piping | Liquid Side/Gas Side | mm | 9.52/19.5 (3/8 x 3/4) |
Max Pipe Length | m | 30 | |
Max High Drop | m | 20 | |
Ambient Temp | Cooling | °C | 18-43 |
Heating | °C | -15~24 |