Call Us On: +27 12 534 3755 (Office)

View Product

Beat the heat this summer, get a free professional aircon quote

60,000 BTU/HR Ducted Split

Product Description

The 60000 BTU Ducted Split from Green Air-Conditioning is best suited for office and industrial use. This aircon will work optimal in rooms and areas with a floor size of up to 100m². Our franchises, agents and dealers are all highly trained professionals and will also be able to assist you with the installation.

Feel free to request a quote or contact us for expert advise.

Specifications Summary

  • Capacity: 60,000 BTU/HR
  • Model: DUCM-H60
  • Refrigerant Type: R410a
Type of Unit DUCTED SPLIT
Model   DUCM-H60
Indoor Power Supply V-Ph-Hz 220~240/1/50 
Cooling Capacity Btu/h 60000
kW 17.60
Input kW 6.26
Rated current  A 11.34
EER W/W 2.60
Heating Capacity Btu/h 63500
Kw 18.50
Input kW 5.78
Rated current A 10.36
COP w/w 3.20
Indoor Fan Motor Model  

FP240A

Output Power x Fan Quantity W 240 x 1
Capacitor uF 12
Speed (Hi/Med/Low) r/min 1385/1240/1160
Indoor Coil Number of Rows   3
Tube Pitch (a) x Row Pitch (b) mm 20.5 x 12.7
 Fin Pitch mm 1.4
 Fin Type   Hydrophilic aluminum
 Tube Outside Dia. and Type mm 7 Inner grooved
Coil length x height x width mm 985 x 328 x 38.1
Number of Circuits   8
Indoor Airflow (Hi/Mi/Lo) m³/h 2600/2300/1950
Indoor noise level (Hi/Mi/Lo) dB(A) 50/47/45
Indoor Unit Dimension (W x D x H) mm  
Packaging (W x D x H) mm  
Net/Gross weight Kg 50/56
External Static Pressure Pa 80
Wireless Remote Controller   XK05-DY
Outdoor Power Supply V-Ph-Hz 380~415/3/50 
Max Input Consumption W 7300
Compressor Model   ATE590SC3Q9JK
Type   Twin Rotary
Brand   Highly
Capacity W 14850
Input W 4950
Rated current  (RLA) A 8.7
Locked rotor (LRA) A 65
Thermal protector Temp.   165
Capacitor uF  /
Refrigerant Oil ml 1850
Outdoor Motor Fan Model   CW60A
Output Power x Fan Quantity W 60 x 2
Capacitor uF 3.5*2
Speed r/min 750
Outdoor Coil Number of rows   1.5
Tube Pitch (a) x Row Pitch (b) mm 22 x 19.05
Fin spacing mm 1.6
Fin type   Hydrophilic aluminum
Tube outside dia. and type mm 7 Inner grooved 
Coil length x height x width mm (918+530) x 1276 x 38.1
Number of circuits   9
Outdoor Airflow Volume m³h / CFM 5800 / 3412
Outdoor noise level dB(A) 60
Outdoor Unit Dimension (W x D x H) mm 940 x 370 x 1325
Packaging (W x D x H) mm 1080 x 430 x 1440
Net/Gross weight Kg 99/109
Refrigerant Type/Quantity g R410a/3000
Design Pressure MPa 4.4/1.4
Connecting Wiring Power Wiring (Indoor) mm² 3 x 1
Power wiring (Outdoor) mm² 5 x 4
Signal wiring mm² 2 × 1
Refrigerant Piping Liquid Side / Gas Side mm 9.52/19.05 (3/8 x 3/4) 
Max Pipe Length m 50
Max High Drop m 30 
Ambient Temp Cooling °C -5~49
Heating °C -15~24
Ducting Supply Air Size mm 975 x 190
Return Air Size mm 1185 x 300
Back to Top