Product Description

The 30kW cooling capacity Air Cooled Modular Chiller from Chigo Air-Conditioning is best suited for office and industrial use. This modular chiller will work optimal in areas with a floor size of up to 170m². Our franchises, agents and dealers are all highly trained professionals and will also be able to assist you with the installation.

Feel free to request a quote or contact us for expert advise.

Specifications Summary

  • AIR COOLED MODULAR CHILLER
  • CLS-F30HW/S
  • 30 kW
  • R410a
Type of Unit AIR COOLED MODULAR CHILLER
Model Number CLS-F30HW/SR1
Capacity Cooling kW 30
Btu/h 8.5
Capacity Heating kW 35
Power Supply V/Ph/Hz 380/3/50
Power Supply Manual switch 100             150
Fuse 50 100
Compressor                                      Type Scroll
Brand Copeland
Model ZP144KCE-TFD-522
Quantity 1
Power Input Cooling kW 11.1
Cooling rated current A 19
Heating kW 10.8
Heating rated current   A 18
Max. Input consumption kW 16
Max. Current A 29
Refrigerant Type R410a
Refrigerant control EXV+Capillary throttle
Weight                                           Kg 7.0
Condenser (Air side) Air side heat exchange              Finned coil pipe type
Fan motor Qty 1
Air flow volume 10³/m³/h 12
Fan motor model YDK550-6S01
Fan motor rated current A 4.2
Fan motor input kW 0.911
Evaporator  (Water side) Water side heat-exchanger Shell and tube
Water resistance loss kPa 30
Water inlet/outlet pipe line inside normal diameter mm DN40
Water flow volume m³/h 5.16
Max. Pressure     MPa 1.1/2.75
Water Pipe connection type Flange connection
Dimension Nett (W x H x D) mm 1160 x 2090 x 900
Packing size (W x H x D) mm 1240 x 2250 x 950
Weight Nett weight Kg 320                                                  
Gross weight Kg 330
Connection wiring Power wiring mm 16mm 2x3+10mm 2x2
Signal wiring mm (0.5~1) mm 2x2
Control Type Wired controller
Safety protection device Power supply protection (lack of phase, sequence, frequence, voltage).
Chiller water pump overload protection
Chiller water shortage protection
Water outlet temp. protection
Compressor discharge temp. protection
Compressor low pressure protection
Compressor high pressure protection
Sensor malfunction protection
Compressor current input protection
Fin temp. (Ambient temp.) protection
Anti-frozen protection
Sound level (semi-anechoic)     dB(A) 62
Operation water temp. Cooling °C 7~25
  Heating °C 30~55
Ambient temperature Cooling °C 10~48
  Heating °C -10~21
Remarks: Specifications are based on the following conditions:
Cooling:  Chilled water inlet/outlet: 12°C / 7°C and outdoor ambient of 35°C DB
Heating:  Warm water inlet/outlet:  40°C 45°C and outdoor ambient temp. 7°C DB/6°CWB    
Water side fouling factor: 0.086m 2°C/kW.    