Call Us On: +27 12 534 3755 (Office)

View Product

Beat the heat this summer, get a free professional aircon quote

60,000 BTU/HR Ducted Split

Product Description

The 60000 BTU Ducted Split from Chigo Air-Conditioning is best suited for home, office and industrial use. This aircon will work optimal in rooms and areas with a floor size of up to 100m². Our franchises, agents and dealers are all highly trained professionals and will also be able to assist you with the installation.

Feel free to request a quote or contact us for expert advise.

Specifications Summary

  • 60,000 BTU/HR
  • CTH-60HR1 (RS485)
  • R410a
Type of Unit DUCTED SPLIT
Model                                                                                                                            CTH-60HR1 (RS485)
Indoor Power Supply                                                             V-Ph-Hz         220~240/1/50 
Cooling Capacity Btu/h 55000
kW 16
Input W 500
Rated current A 2.3
EER W/W 2.58
Heating                                  Capacity Btu/h 60000
Kw 17.6
Input W 500
Rated current A 2.3
COP w/w 2.54
Indoor Fan Motor Model   YDK-139-300F-4P3H95
Input W 500
Capacitor uF 15
Speed (Hi/Med/Low) r/min 1050/830/720
Indoor Coil Number of Rows                   3
Tube Pitch (a) x Row Pitch (b) mm 22 x 19.05
Fin Spacing mm 1.6
Fin Type   Hydrophilic
Tube Outside dia. and Type mm 7.94 Inner grooved
Coil length x height x width mm 935 x 300 x 57.15
Number of Circuits   6
Indoor Airflow (High speed) m³/h 2300
Static Pressure Pa 120
Indoor noise level dB(A) 44-52
Indoor Unit Dimension (W x D x H) Body mm 1175 x 625 x 370
Packaging (W x D x H) Body mm 1245 x 655 x 445
Net/Gross weight Body Kg 45/49
Max Pressure MPa 4.0
Refrigerant Type R410a 
Refrigerant Piping Liquid Side/Gas Side mm 9.52/19.05 (3/8 x 3/4) 
Drainage Pipe mm DN25
Standard Controller   Standard for wired controller (remote controller for option)
Operation Temperature °C 16~32 
Ambient Temperature Cooling °C 18-50 
Heating °C -7~24
Application Area   60~105
Model   COU-60HSR1
Outdoor Power Supply V-Ph-Hz 380~415/3/50 
Cooling Capacity Btu/h 55000
Kw 16
Input W 5700
Rated current A 10
Heating Capacity Btu/h 60000 
Kw 17.6
Input W 5800
Rated current A 10.2
Max Input Consumption W 6600
Max Current A 11.8
Starting current A 85
Compressor Model   QXAS-H64SN330
Type   Rotary
Brand   Landa
Capacity Btu/h 58300
Input W 5450
Rated current (RLA) A 10.6
Locked rotor (LRA) A 85
Thermal protector   Internal
Capacitor uF /
Refrigerant Oil ml 1700
Outdoor Motor Fan Model   YDK-60-6P3-2
Input W 170*2
Capacitor uF 4*2
Speed                                         r/min 780
Outdoor Coil Number of rows                           2
Tube Pitch (a) Test Row Pitch   mm 25 x 21.65
Fin spacing                              mm 1.6
Fin type   Hydrophilic 
Tube outside dia. and type         mm 9.52 Inner grooved 
Coil length x height x width mm 810 x 1275 x 43.3
Number of circuits   7
Outdoor Air flow (High speed) m³h 6100 
Outdoor noise level dB(A) 60
Outdoor Unit Dimension (W x D x H) mm 911 x 400 x 1335
Packaging (W x D x H) mm 964 x 402 x 1445
Net/Gross weight Kg 101/111
Refrigerant Type g R410a/4000
Throttle Part   Capillary 
Design Pressure MPa 4.0 / 1.2
Max Pressure MPa 4.5
Connecting Wiring Outdoor power supply   Separated
Power wiring mm 5 x 2.5 / 3 x 1.0
Signal wiring mm  3 × 0.75
Refrigerant Piping Liquid Side/Gas Side mm 9.52/19.05 (3/8 x 3/4) 
Max Pipe Length m 50 
Max High Drop m 30 
Ambient Temp Cooling °C 18-50
Heating °C -7~24
Ducting Supply Air Size mm 740 X 270
Return Air Size mm 925 X 295
Back to Top