Call Us On: +27 12 534 3755 (Office)

View Product

Beat the heat this summer, get a free professional aircon quote

60,000 BTU/HR Under/Floor Ceiling Inverter Split

Product Description

The 60000 BTU Under/Floor Ceiling Split from Chigo Air-Conditioning is best suited for home, office and industrial use. This energy-saving aircon will work optimal in rooms and areas with a floor size of up to 100m². Our franchises, agents and dealers are all highly trained professionals and will also be able to assist you with the installation.

Feel free to request a quote or contact us for expert advise.

Specifications Summary

  • 60,000 BTU/HR
  • CUA-60HVR1
  • R410a
  • Inverter
Type of Unit UNDER/FLOOR CEILING INVERTER SPLIT
MODEL CUA-60HVR1
Outdoor Power Supply V-Ph-Hz 220~240/1/50 
Cooling Capacity kW 7.8-16.0-17.5
Power input W 1900-5430-6100
Current input A 9.95
EER W/W 2.95
SEER W/W /
Heating Capacity kW 8.5-17.6-19.5
Input W 2.0-5.06-6.5
Rated current A 9.35
COP W/W 3.48
SCOP W/W /
Energy rate Cooling A
Heating            A
Max. power input W 6800
Max. current input A 12.8
Indoor fan motor Model YSK110-85LD-4P2
Brand Yong'an
Power output W 85
Capacitor uF 5
Speed r/min 1560/1430/1300
Insulation class B
Indoor coil Number of rows 4
Tube pitch (a) x row pitch (b) mm 22 x 19.1
Fin spacing mm 1.7
Fin type Hydrophilic
Tube outside dia. and type mm 7.94 Inner grooved
Coil length x height x width mm 1382 x 242 x 76.2
Number of circuits 4
Indoor air flow (High/Speed) m³/h 2000
Indoor noise level Power level dB(A) 57-67
Pressure level 46~52
Indoor unit Dimension (W x D x H) Body mm 1670 x 240 x 680
Packing (W x D x H) Body Kg 1750 x 330 x 765
Net/Gross Weight Body Kg 49/55.5
Max. Pressure Mpa 4.5
Refrigerant Type R410a
Refrigerant piping Liquid side/Gas side mm 9.52/15.88 (3/8 x 5/8)
Drainage pipe mm DN25
Standard controller Standard controller
Operation Temp °C 16~32
Ambient Temp Cooling                                         °C -15~50
Heating °C -15~30
Application area 64-106
MODEL COU-60HZVR1
Outdoor power supply V-Ph-Hz 380-415/03/50
Cooling Capacity kW 16.0 (7.8-17.5)
Power input W 5150
Current input A 8.8
Heating Capacity Kw 17.6 (8.5-19.5)
Power input W 4780
Current input A 8.2
Compressor                                 Model   ATQ420D2UMT
Type   DC/Hermetic Rotary
Brand   GMCC
Frequency range Hz 12~120
Capacity W 12960
Input W 3430
Current (RLA) A 6.85
Refrigerant Oil ml 1400
Outdoor Motor Fan Model YDK-80-6P3-1
Brand Weiling
Power Output W 77
Speed r/min 780/630
Insulation class B
Outdoor Coil Number of rows   2
Tube Pitch (a) Test Row Pitch mm 25 x 21.65
Fin spacing mm 1.6
Fin type   Hydrophilic 
Tube outside dia. and type mm 9.52 Inner grooved 
Coil length x height x width mm 1275 x 802 x 43.3
Number of circuits   7
Outdoor Air flow (High speed) m³h 7200
Outdoor noise level Power level dB(A) 70
Pressure level   58
Outdoor Unit Dimension (W x D x H) mm 950 x 388 x 1335
Packaging (W x D x H) mm 964 x 402 x 1445
Net/Gross weight Kg 98.2/106.5
Refrigerant Type g R410a/4100
Throttle Part   EXV
Design Pressure MPa 4.5/1.6
Max Pressure MPa 4.5
Connecting Wiring Power wiring mm 5x2.5
Signal wiring mm 3x1.0
Refrigerant Piping Liquid Side / Gas Side mm 9.52/15.88 (3/8 x 5/8) 
Max Pipe Length m 65
Max High Drop m 30
Ambient Temp Cooling °C -5~50
Heating °C -15~30
       
Back to Top